Sign In | Join Free | My entremaqueros.com |
|
Brand Name : P+F
Model Number : Repeater KFD0-CS-Ex2.50P
Certification : CE
Place of Origin : Indonesia
MOQ : 1pc
Price : negotiable
Payment Terms : T/T
Supply Ability : 100pcs per month
Delivery Time : 12-16weeks
Packaging Details : standard carton packing
Signal type : Analog input/analog output
Safety Integrity Level (SIL) : SIL 2
Systematic capability (SC) : SC 3
Rated voltage : 5 ... 35 V DC , loop powered
Current : 4 ... 20 mA
Dimensions : 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
This isolated barrier is used for intrinsic safety applications. The device can be used as a repeater or transmitter power supply for 2-wire transmitters. This device is loop powered. No additional power supply has to be connected. Use the technical data to verify that proper voltage is available to the field devices.
General specifications |
||
---|---|---|
Signal type |
Analog input/analog output |
|
Functional safety related parameters |
||
Safety Integrity Level (SIL) |
SIL 2 |
|
Systematic capability (SC) |
SC 3 |
|
Supply |
||
Rated voltage |
5 ... 35 V DC , loop powered |
|
Control circuit |
||
Connection |
terminals 12-, 11+; 8-, 10-, 9+ |
|
Voltage |
5 ... 35 V DC |
|
Current |
4 ... 20 mA |
|
Power dissipation |
at 20 mA and Uin < 24.3 V: < 250 mW per channel |
|
Field circuit |
||
Connection |
terminals 1+, 2-; 4+, 5- |
|
Voltage |
for 5V < Uin < 24.3V: ≥ 0.9 x Uin - (0.37 x current in mA) - 1.0 |
|
Short-circuit current |
at Uin > 24.3 V : ≤ 65 mA |
|
Transfer current |
≤ 40 mA |
|
Transfer characteristics |
||
Accuracy |
0.1 % |
|
Deviation |
|
|
|
After calibration |
≤ ± 20 µA; incl. calibration, linearity, hysteresis and load fluctuations at the field side up to a load of 1 kΩ at 20 °C (68 °F) |
|
Influence of ambient temperature |
≤ ± 2 µA/K at Uin ≤ 20 V; ≤ ± 5 µA/K at Uin > 20 V |
Rise time |
≤ 5 ms at bounce from 4 ... 20 mA and Uin < 24 V |
|
Galvanic isolation |
||
Field circuit/control circuit |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
|
Indicators/settings |
||
Labeling |
space for labeling at the front |
|
Directive conformity |
||
Electromagnetic compatibility |
|
|
|
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
Conformity |
||
Electromagnetic compatibility |
NE 21:2012 |
|
Degree of protection |
IEC 60529:2001 |
|
Protection against electrical shock |
UL 61010-1:2012 |
|
Ambient conditions |
||
Ambient temperature |
-20 ... 70 °C (-4 ... 158 °F) |
|
Mechanical specifications |
||
Degree of protection |
IP20 |
|
Connection |
screw terminals |
|
Mass |
approx. 100 g |
|
Dimensions |
20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1 |
|
|
Height |
107 mm |
|
Width |
20 mm |
|
Depth |
115 mm |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
|
Data for application in connection with hazardous areas |
||
EU-type examination certificate |
BAS 98 ATEX 7343 X |
|
|
Marking |
|
|
Voltage |
25.2 V |
|
Current |
93 mA |
|
Power |
585 mW |
Control circuit |
|
|
|
Maximum safe voltage |
250 V eff (Attention! The rated voltage can be lower.) |
Field circuit |
|
|
|
Maximum safe voltage |
250 V eff (Attention! The rated voltage can be lower.) |
Certificate |
FIDI 22 ATEX 0001 X |
|
|
Marking |
|
Galvanic isolation |
|
|
|
Field circuit/control circuit |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity |
|
|
|
Directive 2014/34/EU |
EN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018 |
International approvals |
||
FM approval |
|
|
|
Control drawing |
116-0437 |
UL approval |
E106378 |
|
|
Control drawing |
116-0438 (cULus) |
IECEx approval |
|
|
|
IECEx certificate |
IECEx BAS 05.0004X |
|
IECEx marking |
[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |
![]() |
P+F Repeater KFD0-CS-Ex2.50P with SC 3 Systematic Capability 5 ... 35 V DC Images |